Technical-economical evaluation of a solar water heater with vacuum tubes collector, used in a rural area in Paraná, Brazil

Carlos Eduardo Camargo Nogueira
  • Carlos Eduardo Camargo Nogueira
  • College of Post-Graduation Program of Energy Engineering in Agriculture (PPGEA), from State University of Western Parana (UNIOESTE), Rua Universitária, 2069, CEP: 85.819-110, Cascavel, PR, Brazil.
  • Google Scholar
Gilberto Carlos Arnauts
  • Gilberto Carlos Arnauts
  • College of Post-Graduation Program of Energy Engineering in Agriculture (PPGEA), from State University of Western Parana (UNIOESTE), Rua Universitária, 2069, CEP: 85.819-110, Cascavel, PR, Brazil.
  • Google Scholar
Joao Carlos Munhoz das Neves
  • Joao Carlos Munhoz das Neves
  • College of Post-Graduation Program of Energy Engineering in Agriculture (PPGEA), from State University of Western Parana (UNIOESTE), Rua Universitária, 2069, CEP: 85.819-110, Cascavel, PR, Brazil.
  • Google Scholar
Samuel Nelson Melegari de Souza
  • Samuel Nelson Melegari de Souza
  • College of Post-Graduation Program of Energy Engineering in Agriculture (PPGEA), from State University of Western Parana (UNIOESTE), Rua Universitária, 2069, CEP: 85.819-110, Cascavel, PR, Brazil.
  • Google Scholar


  •  Received: 22 October 2014
  •  Accepted: 07 April 2015
  •  Published: 23 April 2015

 ABSTRACT

Solar radiation is a source of energy that can be used directly by residences and industries. In this work, the efficiency of a solar collector type all-glass installed in a rural area in Paraná, Brazil, in the winter period, was evaluated.  Two daily showers were simulated in three different scenarios, to measure additional electrical consumption used to boost the heating of water. In the first scenario, the consumption was evaluated leaving the auxiliary heating system connected the entire day and, in the second, only in the afternoon period. This auxiliary heating system, controlled by a thermostat, was only connected when the temperature of the water in the boiler stayed below 40°C. In the third scenario, the auxiliary heating system was disconnected and the heating of the water occurred solely due to the solar heating system. These scenarios were compared with the use of the solar heating system together with an electric shower and with an electric shower alone. It was verified that the mean efficiency of the solar collector in the evaluated period was 51%. The electric shower, when used in conjunction with the solar heater, consumes 6.5 times less electrical energy than when used alone (192.55 kWh and 1240.34 kWh, respectively). 

 

Key words:  Renewable energy, vacuum solar collector, solar water heater.


 INTRODUCTION

In 2013, the Brazilian electrical consumption per residency was of 124.858 GWh, which represented 27% of the country’s consumption (Brasil, 2014). Of these, 24% were directed to the electric shower of the residency, in other words, 30.000 GWh were intended for the heating of water (Penereiro et al., 2010).
 
According to   Mogawer and  Souza (2004),  almost   all  this energy is used during peak hours (between 18 h and 20 h),  overloading the electrical system. This demand represents about 12.8% of the total need in this period, which corresponds to approximately 6.800 MW of installed power, almost half of the current 14.000 MW  Itaipu Hydroelectric Plant's capacity, Paraná.
 
Use of  conventional  sources  of  energy  to  meet  this demand causes ecological problems and reduction in supply. A possible solution though is the use of alternative sources of energy (Kousksou et al., 2014). The use of solar energy has intensified in Brazil, taking advantage of its high solar radiation index (Aldabó, 2002).
 
The South of Brazil has a high usage of electric showers, which means, despite being the region with the smallest solar radiation of Brazil, can contribute with the use of solar heaters, following the example of European countries, that intensely use this technology, despite its solar radiation being a little lower (Pereira et al.,  2006).
 
One of the biggest implementation of this technology is established in India, in an industrial egg processing plant, where 1280 panels heat 110.000 L of water to 85°C, equivalent to a 1 MW power station, generating 78% saving of fuel oil (Nagaraju et al., 1999). Thus, the substitution of conventional heating by solar may be a great  economic  alternative,  in   order   to   reduce  peak hour’s electrical consumption in the country (Prado, 2007; Naspolini and Rüther, 2011).
 
Nevertheless, the high initial cost of this technology can be a negative factor. Moreover, the auxiliary heating for days with low solar radiation can use up a lot of energy, turning the system unviable. The project directly influences the efficiency (Wang et al., 2015), thus, diverse forms of this technology have arrived in the country in the last years, including, the solar water heater with vacuum tube collectors. These tubes have higher efficiency as they make more use of solar radiation, independent of the angle of occurrence of the same (Goerck, 2008). This fact is very important, because the dependence of the angle may be very significant in other systems (Elhab et al., 2012).
 
The aim of this work was to calculate the efficiency of a solar heating system with vacuum tubes collector, and verify its economic viability using three distinct scenarios.


 MATERIALS AND METHODS

This experiment took place during the period of 1st June to 31st August 2013, at State University of Western Paraná, situated in the city of Cascavel, Latitude 24°59’ South, Longitude 58°23’ west and means altitude of 785 m. In this location, a vacuum tube solar water heater was connected to a boiler EXXA brand, with 1.6 x 2.6 m dimensions. It was installed facing north, with a 28° inclination. The collector shown in Figure 1, of the type all glass is made up of 20 glass tubes, directly connected to thermal reservoir. 
 
 
This reservoir has 170 L of capacity and an electrical heating system of 1500 W.  Above the thermal reservoir there is a small feeder tank, with a floating ball-cock. The water from this tank flows through an internal tube to a boiler, while the water heated by the collector rises by convection to the top of the reservoir. The design of the hydraulic system is highlighted in Figure 2.
 
 
Equipment used for measuring and recording data
 
Datalogger
 
Data regarding temperature, electric current and solar radiation was collected every 10 s using a datalogger CR1 1000 model, of Campbell Scientific manufacture, which has 8 analogue inputs. A 12 V output was also used to power a contact that activates the electrical heating system of boiler when necessary, based on temperature of the water.
 
Thermocouple
 
Six thermocouples type J were used to measure temperature, interconnected to the data measuring system. Such thermocouples have mineral insulation with metal protection, allowing for them to be installed and used in direct contact with water. The diagram in Figure 3 shows the location of the temperature sensors in heater.
 
 
Pyranometer
 
The measuring of solar radiation was completed using a pyrometer of Kipp & Zonen manufacture; model CMP3, with sensitivity of 15.0 µV W-1 m-2.  It was installed close to the heater,  and  the  values  of radiation measured were stored by the datalogger every 10 s.
 
Devices used for control and signaling
 
Solenoid valve
 
The hot water exit was controlled by a double solenoid valve; model EVA-03 of EMICOL manufacture, controlled by a remote switch. It has 3/4”connection and 220 V power.
 
Timer, relay and contact
 
A timer was installed to control the running of the auxiliary heating system of the boiler, of Logica 600 model and Kienzle manufacture, like a  relay  and  a  contact  controlled by  12V  from  a  datalogger.
 
Installation diagram
 
The electrical installation to power the auxiliary heating system and the solenoid valve followed NBR 5410/2004 standards - Electrical installation of low voltage (ABNT, 2004). Its electrical connections are indicated in Figure 4.
 
 
Methodology
 
Daily consumption of hot waters
 
The daily consumption of hot water during the entire period of the experiment was set to two showers occurring at the end of the afternoon, with temperature of water being around 40°C, and 60 L of volume per shower. As temperatures of hot and cold water vary daily, a mixer of water was simulated for this occurrence. The output of hot water eliminated through the solenoid valve was measured, obtaining the constant amount of 6 L min-1. Thus, through the time variation operating time of this valve, it was possible to obtain the volume of hot water that would be necessarily added to the cold water, to obtain a mixture of water of 40°C temperature. This timing was calculated using Equation 1, developed by the author. The values of hot and cold water used in the equation were obtained directly from recorded measurements in datalogger, moments before each simulation.
 
 
Scenarios for the use of solar heater system
 
The datalogger was programmed to turn on the auxiliary heating system of the boiler when its temperature fell below 40°C. There were three scenarios for the installed system:
Scenario I - With the timer on "ON position”,  the auxiliary heating system stays connected and can be turned on any hour of the day, as needed to heat water.
Scenario II – The timer set in "automatic position” allows connection to auxiliary resistance between 12:00 and 18:00 hours only.
Scenario III – The timer on "OFF position” does not connect to the auxiliary heater at any time and the heating occurs only as a function of solar radiation.
The setting of the timer was changed at the end of each day, to sequence through the scenarios. Other than the scenarios studied, two simulations using an electric shower were used:
Simulation I – The shower is connected to the solar heating system in scenario III, and is used, when necessary, to boost temperature of "preheated" water.
Simulation II – The electric shower works alone, without any solar heating system to preheat the water.
 
Processing of data
 
Efficiency of solar heater calculation
 
The mean efficiency  of  the  solar  heating  system  was  calculated from data gathered between 6:00 and 18:00 h each day, and is given in Equation 2 (Duffie and Beckman, 2006):
 
 
Calculation of energy balance of the system
 
The energy balance of the system was calculated using Equation 5, so that energy gained were due to incidence of solar radiation and the functioning of the auxiliary electric heating; and the losses of energy were due to losses through the walls of the boiler and replacement of cold water (Duffie and Beckman, 2006):
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 


 RESULTS AND DISCUSSION

Analysis of efficiency of solar heater
 
The efficiency of the collector was calculated using Equation 2, resulting in a mean value of 51%. Goerck (2008) evaluated a solar water heater with vacuum tubes collector with heat pipe in the region of Taquari (Rio Grande do Sul), estimating its efficiency to 43%.
 
Extraction factor of the collector (FR) and thermal coefficient of boiler (U)
 
The factors UA and FR were determined from Equation 5, using simulations performed with the Matlab 2012 software. The optimum value obtained for the FR (extraction factor of collector) was of 0.62 with values ranging between 0.50 and 1.0 in increments of 0.01. For UA (product of thermal coefficient of the boiler by its external area), the optimum value was of 3.5, with values varying from 2 to 10, in increments of 0.5. Sabs (2009) has found the coefficient of 3.878 for various reservoirs exposed to open air. The optimum values obtained were the ones that presented the best fit of temperature measured data and of solar radiation to equation of energy balance.
 
Functioning of heater evaluation
 
Table 1 compares the performance and consumption of energy from the heater in the three scenarios. The third column of the table details the days in which the temperature remained above 40°C. In scenario 1, the consumption of  electrical  energy  measured  in 46 days, due to the operation of the auxiliary heating system, was of 436 kWh (average of 9.48 kWh day-1). In the days in which the heater operated in Scenario 2, the temperature of the boiler also remained above 40°C at the end of the afternoon. The measured consumption of electrical energy was of 38.9 kW (mean of 2.59 kWh day-1). It is noted that the insertion of the timer in the circuit in scenario 2, to limit the operation of the auxiliary heater only to the afternoon period, reduced in 72.68% the mean daily consumption in relation to scenario 1. In scenario 3, in 14 days (of a total of 28), the temperature of the boiler at 17 h was lower than the set temperature.
 
 
Evaluation of the use of solar collector as a preheater for an electric shower
 
The results obtained in Scenario 3 were used to make Table 2, which simulates the energy that would be consumed by an electric shower to heat water up to the required temperature for showers, from the preheated water by  the  solar  heater,  and  from  the  natural  water (cold). The results of the fourth and fifth column were calculated considering a water mass equal to 120 kg at 40°C (2 showers). 
 
 
In the fourth column are the values calculated to complement the thermal energy needed to reach the set temperature of consumption from the temperature of water preheated by solar energy. This energy would be supplied by an electric shower with variable power that would consume a daily average of 1.11 kWh (Simulation I).
 
The last column shows calculated values of energy that would be consumed in the same days by a shower, also electrical, to raise the temperature of the cold water to 40°C (Simulation II). The daily mean consumption of 2.81 kWh of the shower would be, in this case, about, 1.5 times the consumption obtained when the preheated water with solar energy is used by the shower supply. Of the five ways of operating the solar heater analyzed (Scenario I, II and III; Simulation I and II), the best result would be the one that meets the requirements of showers every day, with the least consumption of electrical energy.
 
Annual saving of combined use of electric shower with solar heater
 
Table 3 shows a simulation of annual saving obtained when using an electric shower of variable power to heat water from an initial temperature (cold or preheated by solar heater) up to the desired temperature for a shower (about 40°C). Figure 5 shows a comparison between the energy consumed by shower using preheated water, with the energy consumed by shower using cold water, to reach the desired temperature. These data were obtained from columns 4 and 6 of Table 3.
 
 
 
The  simulation  shown  in Table 3  indicates  an annual saving of US$ 200.83, obtained by reduction of consumption of electric energy of a shower fed with water preheated by solar energy (annual cost of US$ 36.90), when compared with a shower fed with cold water from supply network (annual cost of US$ 237.73). The cost of US$ 0.1916 per kWh of electrical energy is applied to consumers in residential category (COPEL, 2013).
 
The temperature of the preheated water, in the third column of the table, was estimated based on potential heating of solar collector when exposed to the mean monthly radiation in the West of Paraná (Pereira, 2002). The values of additional energy, in the fourth column, are of thermal energy necessary for the water, already preheated by the solar collector, to reach 40°C. There is a greater need of extra electrical energy between May and August, because these months coincide with smaller values of ambient temperature and solar radiation. However, in the month of April, a lower radiation is compensated by higher ambient temperature, while in September the opposite occurs.
 
The table was created taking into account that the water stored is at ambient temperature. Therefore, the constant temperature of the cold water in the fifth column was considered equal to the lowest average ambient temperature registered in the city of Cascavel between 1972 and 2009 (Lima, 2012). The values in the last column show the necessary energy for a shower to reach the set temperature for showering, when fed with cold water from supply network. 
 
Economic analysis of investments
 
Table 4 shows data used to make financial analysis of investments. Table 5 presents a comparative economic analysis for the five options of heating water for showering. Analyzing Table 5, it can be noted that option "Scenario 1" has the highest annual cost (US$ 579.65), followed by option 'Simulation 2" (US$ 241.89). Option "Scenario 3" has the smallest annual cost; it however, does not meet the water temperature requirements in the coldest months. The options "Scenario 2" and "Simulation 1" are practically the same, since the latter has an annual cost a little less than the former. Column 4 shows return time of investment (payback completion), in accordance with Newnan et al., (2011).
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 


 CONCLUSIONS

The mean efficiency found for the model of solar heater in study was of 51%. Three scenarios with solar heater were evaluated and 2 simulations with an electric shower were made. In scenario 1, the daily average energy consumption was of 9.48 kWh (auxiliary heating system connected without time restriction). In scenario 2 (working hours of auxiliary heating system restricted to the afternoon period), the daily average consumption was of 2.59 kWh, in other words, 72.68% lower than the previous.
 
In scenario 3 (auxiliary heating system turned off), 14 of the 28 days that the heater functioned, the water temperature at the end of the afternoon was lower than set, which makes this form of operation unviable.  Simulating the energy that would be necessary for an electric shower to boost the temperature of water in these 14 days in Scenario 3, a daily mean consumption of 1.11kWh can be observed (Simulation I) against 2.81kWh (Simulation II), which would have been used by the same shower, if it were directly fed with cold water from network supply.
 
The annual costs of these ways of operating were calculated and compared, revealing that simulation I presents smaller cost and is more interesting due to flexibility of operating times of hot water. Finally, it was established that the return of investment in the installation of a solar heater connected to an electric shower, for an interest rate of 6% per year, occurs in about 7 years, when compared with using an electric shower alone.


 CONFLICT OF INTEREST

The authors have not declared any conflict of interest.



 REFERENCES

ABNT (2004). NBR 5410- Instalações elétricas de baixa tensão. Rio de Janeiro.
 
Aldabó R (2002). Energia Solar. São Paulo. Artiliber Editora.
 

Brasil, Agência (2015). Consumo de energia elétrica cresceu 3.5% em 2013. Rio de Janeiro. 2014.

View

 
COPEL (2013). Taxas e tarifas. 
 
Duffie JA, Beckman WA (2006). Solar engineering of thermal processes. 3ª ed. New Jersey. Wiley.P. 928.
 
Elhab BR, Sobian K, Mat S (2012). Optimizing tilt angles and orientations of solar panels for Kuala Lumpu, Malaysia. Solar Energy Research Institute (SERI), Level 3. Malaysia.
 
EXXA SOLAR (2009). Sistema de aquecimento solar - tubos a vácuo. Manual de Instalação.
 
Goerck M (2008). Determinação do potencial energético de um coletor solar foto térmico na região do vale do Taquari – RS Brasil. Lajeado. Centro Universitário Univates. Dissertação (Mestrado em Ambiente e Desenvolvimento). P. 92.
 
Kousksou T, Bruel P, Jamil A, Rhafiki EI, Zeraouli Y (2014). Energy storage: Applications and challenges. Solar Energy Materials and Solar Cells. France.
Crossref
 
Lima CB (2012). Análise da variação das temperaturas mínimas para Cascavel – PR. Revista Brasileira de Energias Renováveis, 1:1-21.
 

Mogawer T, Souza TM (2004). Sistema Solar de Aquecimento de Água para Residências Populares. In. V Encontro de Energia do Meio Rural. Campinas. Anais eletrônicos.

View

 
Nagaraju J, Garud SS, Kumar KA, Rao MR (1999). 1 MWth Industrial solar hot water system and its performance. Solar Energy. [S.l.], 66(6):491-497.
 
Naspolini HF, Rüther R (2011). The impacts of solar water heating in low-income households on the distribution utility's active, reactive and apparent power demands. Solar Energy. Federal University of Santa Catarina. Florianópolis, Santa Catarina.
Crossref
 
Newnan D, Eschenbach T, Lavelle J (2011). Engineering Economics Analysis. 11ª edição. Oxford University Press.
 
Penereiro JC, Melo LP, Coradi TB (2010). Construção de um aquecedor solar de baixo custo sem cobertura: análise experimental da eficiência térmica para vários ensaios. Revista de ciência & tecnologia. Nova Iguaçu - Rio de Janeiro. 10:1 (Jun-2010). Gráfica Universitária.
 
Pereira AB (2002). Estimativa da radiação solar global diária em função do potencial de energia solar na superfície do solo. Scientia Agricola, 59(2):211-216, Apr./Jun.
Crossref
 
Pereira EB, Martins FR, Abreu SL, Ruther R (2006). Atlas Brasileiro de Energia Solar. 1ª. ed. São José dos Campos. INPE.
 
Prado RTA (2007). Levantamento do estado da arte: Energia solar. Projeto tecnologias para construção habitacional mais sustentável. São Paulo Projeto FINEP 2386/04.
 
Sabs Commercial (Pty) Ltd (2013). Test report SANS 6211-1:2003. Pretória. 2009. 
 
Tiba C, Fraidenraich N (2000). Atlas Solarimétrico do Brasil. Grupo de Pesquisas em Fontes Alternativas de Energia, Departamento de Energia Nuclear. Recife - PE.
 